The Industrial WorkhorseModel: CIMR-F7Z200V Class 3-phase 0.4 to 110 kW400V Class 3-phase 0.4 to 300 kWManual No. I66E-E
EN-9Main Circuit TerminalsMain circuit terminal functions are summarized according to terminal symbols in Table 1. Wire theterminals correctly for th
EN-10Fig 6 Flywheel Diode ConnectionDigital output signalsM1During run (NO) Closed during RunFunction selected by H2-01 to H2-03Relay contactsContact
EN-11 Sinking/Sourcing Mode (NPN/PNP Selection)The input terminal logic can be switched over between sinking mode (0-V common, NPN) andsourcing mode
EN-12 Wiring Main Circuit InputsInstalling FusesTo protect the inverter, it is recommended to use semiconductor fuses like they are shown in thetable
EN-13• If an earth leakage breaker is used, it should be able to detect all kinds of current in order toensure a safe earth leakage current detection•
EN-14Keypad Operation Digital Operator Display (optional)The key names and functions of the Digital Operator are described below Digital Operator Ke
EN-15Power Up and Basic Parameter Setup Start Up ProcedureFig 8 Trial Operation FlowchartYES*6*6*4Motor operation possible during autotuning?*3Setti
EN-16 Before Power UpThe following points should be checked carefully before the power is switched on.• Check if the power supply meets the inverter
EN-17motor parameters will be set automatically. The remaining motor parameters will be set automati-cally during the first time operation.Non-rotatin
EN-18Param-eter Num-berName DescriptionInitialize DataA1-00Language selection for Digital Opera-tor dis-play(JVOP-160-OY only)0:English2:German3:Frenc
F7Z Quick Start GuideTable of ContentsWarnings ... EN-2 Safety Precautions and Ins
EN-19E1-04Max. output frequency (FMAX)To set V/f characteristics in a straight line, set the same values for E1-07 and E1-09. In this case, the settin
EN-20Torque Limit (only OLV and CLV)L7-01Forward drive torque limitSets the torque limit vlaue as a per-centage of the motor rated torque. Four indivi
EN-21Troubleshooting General Faults and AlarmsFaults and Alarms indicate unsusal inverter / application conditions. An alarm does not necessarily swi
EN-22OCOver CurrentOver CurrentThe Inverter’s output current exceeded the over-current detection level.• Remove the motor and run the Inverter withou
EN-23 Operator Programming ErrorsAn Operator Programming Error (OPE) occurs when two or more parameter related to each otherare set inappropriately o
EN-24 Autotuning FaultsAutotuning faults are shown below. When the following faults are detected, the fault is displayed onthe digital operator and
EN-2WarningsCAUTIONCables must not be connected or disconnected, nor signal tests carried out, while the power is switched on.The Varispeed F7 DC bus
EN-3 Safety Precautions and Instructions GeneralPlease read these safety precautions and instructions for use thoroughly before installing and oper-
EN-4 Electrical ConnectionCarry out any work on live equipment in compliance with the national safety and accident preventionregulations. Carry out e
EN-5 Laying CablesMeasures Against Line-Borne Interference:Line filter and frequency inverter must be mounted on the same metal plate. Mount the two
EN-6Installation Mechanical Installation Unpacking the InverterCheck the following items after unpacking the inverter. If any irregularities in the
EN-7 Installation OrientationInstall the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter,always provide the
EN-8 Electrical ConnectionWiring the InverterFig 4 Wiring DiagramTTerminating resistanceP++--IGMEMOBUS communicationRS-485/422PPR+R-S+S-Shielded wi